Normal view

There are new articles available, click to refresh the page.
Today — 18 June 2024US-CERT Current Activity

CISA Releases One Industrial Control Systems Advisory

By: CISA
18 June 2024 at 08:00

CISA released one Industrial Control Systems (ICS) advisory on June 18, 2024. These advisories provide timely information about current security issues, vulnerabilities, and exploits surrounding ICS.

CISA encourages users and administrators to review the newly released ICS advisories for technical details and mitigations.

CISA and Partners Release Guidance for Modern Approaches to Network Access Security

By: CISA
18 June 2024 at 08:00

Today, CISA, in partnership with the Federal Bureau of Investigation (FBI), released guidance, Modern Approaches to Network Access Security, along with the following organizations: 

  • New Zealand’s Government Communications Security Bureau (GCSB); 
  • New Zealand’s Computer Emergency Response Team (CERT-NZ); and 
  • The Canadian Centre for Cyber Security (CCCS).

The guidance urges business owners of all sizes to move toward more robust security solutions—such as Zero Trust, Secure Service Edge (SSE), and Secure Access Service Edge (SASE)—that provide greater visibility of network activity. Additionally, this guidance helps organizations to better understand the vulnerabilities, threats, and practices associated with traditional remote access and VPN deployment, as well as the inherent business risk posed to an organization’s network by remote access misconfiguration.

CISA and its partners encourage leaders to review the guidance to help with the prioritization and protection of remote computing environments.

For more information and guidance on protection against the most common and impactful tactics, techniques, and procedures for network access security, visit CISA’s Cross-Sector Cybersecurity Performance Goals. For more information on zero trust, visit CISA’s Zero Trust Maturity Model

RAD Data Communications SecFlow-2

By: CISA
18 June 2024 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.7
  • ATTENTION: Exploitable remotely/low attack complexity/public exploits are available
  • Vendor: RAD Data Communications
  • Equipment: SecFlow-2
  • Vulnerability: Path Traversal

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to obtain files from the operating system by crafting a special request.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following RAD Data Communications products are affected:

  • SecFlow-2: All versions

3.2 Vulnerability Overview

3.2.1 PATH TRAVERSAL: '..\FILENAME' CWE-29

RAD SecFlow-2 devices with Hardware 0202, Firmware 4.1.01.63, and U-Boot 2010.12 allow URIs beginning with /.. for Directory Traversal, as demonstrated by reading /etc/shadow.

CVE-2019-6268 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2019-6268. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Communications
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Israel

3.4 RESEARCHER

CISA discovered a PoC (Proof of Concept) and reported it to RAD Data Communications.

4. MITIGATIONS

RAD Data Communications reports that SecFlow-2 is EOL (End-Of-Life) and recommends upgrading to the more secure RAD SecFlow-1p product line.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • June 18, 2024: Initial Publication
Before yesterdayUS-CERT Current Activity

Motorola Solutions Vigilant License Plate Readers

By: CISA
13 June 2024 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.7
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Motorola Solutions
  • Equipment: Vigilant Fixed LPR Coms Box (BCAV1F2-C600)
  • Vulnerabilities: Authentication Bypass Using an Alternate Path or Channel, Cleartext Storage in a File or on Disk, Use of Hard-coded Credentials, Insufficiently Protected Credentials, Missing Encryption of Sensitive Data, Authentication Bypass by Capture-replay

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to tamper with the device, access sensitive information and credentials, or perform a replay attack.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Motorola Vigilant License Plate Readers are affected:

  • Vigilant Fixed LPR Coms Box (BCAV1F2-C600): Versions 3.1.171.9 and prior

3.2 Vulnerability Overview

3.2.1 AUTHENTICATION BYPASS USING AN ALTERNATE PATH OR CHANNEL CWE-288

The affected product is vulnerable to an attacker modifying the bootloader by using custom arguments to bypass authentication and gain access to the file system and obtain password hashes.

CVE-2024-38279 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.6 has been calculated; the CVSS vector string is (AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2024-38279. A base score of 5.1 has been calculated; the CVSS vector string is (CVSS4.0/AV:P/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.2.2 CLEARTEXT STORAGE IN A FILE OR ON DISK CWE-313

An unauthorized user is able to gain access to sensitive data, including credentials, by physically retrieving the hard disk of the product as the data is stored in clear text.

CVE-2024-38280 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.8 has been calculated; the CVSS vector string is (AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-38280. A base score of 7.0 has been calculated; the CVSS vector string is (CVSS4.0/AV:P/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.3 USE OF HARD-CODED CREDENTIALS CWE-798

An attacker can access the maintenance console using hard coded credentials for a hidden wireless network on the device.

CVE-2024-38281 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.0 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-38281. A base score of 8.6 has been calculated; the CVSS vector string is (CVSS4.0/AV:A/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.4 INSUFFICIENTLY PROTECTED CREDENTIALS CWE-522

Utilizing default credentials, an attacker is able to log into the camera's operating system which could allow changes to be made to the operations or shutdown the camera requiring a physical reboot of the system.

CVE-2024-38282 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-38282. A base score of 8.5 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.5 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

Sensitive customer information is stored in the device without encryption.

CVE-2024-38283 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.6 has been calculated; the CVSS vector string is (AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2024-38283. A base score of 5.1 has been calculated; the CVSS vector string is (CVSS4.0/AV:P/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.2.6 AUTHENTICATION BYPASS BY CAPTURE-REPLAY CWE-294

Transmitted data is logged between the device and the backend service. An attacker could use these logs to perform a replay attack to replicate calls.

CVE-2024-38284 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-38284. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.7 INSUFFICIENTLY PROTECTED CREDENTIALS CWE-522

Logs storing credentials are insufficiently protected and can be decoded through the use of open source tools.

CVE-2024-38285 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.8 has been calculated; the CVSS vector string is (AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-38285. A base score of 7.0 has been calculated; the CVSS vector string is (CVSS4.0/AV:P/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Emergency Services
  • COUNTRIES/AREAS DEPLOYED: United States
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

The Michigan State Police Michigan Cyber Command Center (MC3) reported these vulnerabilities to CISA.

4. MITIGATIONS

Motorola Solutions recommends the following for each identified vulnerability:

CVE-2024-38279:

  • Use secure boot implementation with an edit-resistant GRUB partition.
  • Additional mitigation consists in limiting the physical access to the device by following the best practices for device mounting.

Edit-resistant grub partition has been remediated for all vulnerable systems. Motorola Solutions
will release a secure boot implementation in Fall 2024. All customers will receive the update
through OTA (over the air) mechanisms. No further actions are required by customers.

CVE-2024-38280:

  • Apply encryption to all Criminal Justice Information (CJI) data.
  • Apply full disk encryption with LUKS encryption standards and add password protection
    to the GRUB Bootloader.
  • Perform column-level encryption for sensitive data in the database.

All devices shipped after May 10, 2024 are already using full disk encryption. All devices that
are not able to have full disk encryption applied have had all CJI data encrypted. No further
actions are required by customers.

CVE-2024-38281:

  • Remove the hard-coded credential to access the wireless access point and disable the
    access point if not needed.
  • Set a unique SSID and password if the access point is needed.

Motorola Solutions has already remediated this vulnerability for all vulnerable systems. No further actions are required by customers.

CVE-2024-38282:

  • Remove the hard coded credentials.
  • Use a unique CJIS compliant password per device.

Motorola Solutions has already remediated this vulnerability for all vulnerable systems. No further actions are required by customers.

CVE-2024-38283:

  • Remove the hotlist data from the device.

Motorola Solutions has already remediated this vulnerability for all vulnerable systems. No
further actions are required by customers.

CVE-2024-38284:

  • Delete the log files.
  • Install updated software not logging the credentialed web request.

Motorola Solutions has already remediated this vulnerability for all vulnerable systems. No further actions are required by customers.

CVE-2024-38285:

  • Delete the log files.

Motorola Solutions has already remediated this vulnerability for all vulnerable systems. No further actions are required by customers.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • June 13, 2024: Initial Publication

Siemens Mendix Applications

By: CISA
13 June 2024 at 08:00

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). 

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 7.4
  • ATTENTION: Exploitable remotely
  • Vendor: Siemens
  • Equipment: Mendix Applications
  • Vulnerability: Improper Privilege Management

2. RISK EVALUATION

Successful exploitation requires to guess the identification of a target role which contains the elevated access rights.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Siemens products, are affected:

  • Siemens Mendix Applications using Mendix 9: Versions prior to V9.24.22 and after V9.3.0
  • Siemens Mendix Applications using Mendix 10: Versions prior to V10.11.0
  • Siemens Mendix Applications using Mendix 10 (V10.6): Versions prior V10.6.9

3.2 Vulnerability Overview

3.2.1 IMPROPER PRIVILEGE MANAGEMENT CWE-269

Affected applications could allow users with the capability to manage a role to elevate the access rights of users with that role. Successful exploitation requires to guess the id of a target role which contains the elevated access rights.

CVE-2024-33500 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:H/UI:N/S:U/C:H/I:H/A:N).

A CVSS v4 score has also been calculated for CVE-2024-33500. A base score of 7.4 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:P/PR:H/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities, Critical Manufacturing, Defense Industrial Base, Energy, Financial Services, Government Facilities, Healthcare and Public Health, Transportation Systems
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Achmea Security Assessment Team reported this vulnerability to Siemens.

4. MITIGATIONS

Siemens recommends users update the product to following versions:

  • Mendix Applications using Mendix 9: Update to V9.24.22 or later version
  • Mendix Applications using Mendix 10: Update to V10.11.0 or later version
  • Mendix Applications using Mendix 10 (V10.6): Update to V10.6.9 or later version

    Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • Set the runtime setting StrictReferenceChecks to false; note however, that this comes at the price of making the reference checks less secure

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-540640 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability has a high attack complexity.

5. UPDATE HISTORY

  • June 13, 2024: Initial Publication

Siemens ST7 ScadaConnect

By: CISA
13 June 2024 at 08:00

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). 

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 8.2
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: ST7 ScadaConnect
  • Vulnerabilities: Integer Overflow or Wraparound, Double Free, Improper Certificate Validation, Inefficient Regular Expression Complexity, Improper Check for Unusual or Exceptional Conditions, Improper Input Validation, NULL Pointer Dereference, Missing Encryption of Sensitive Data, Improper Restriction of Operations within the Bounds of a Memory Buffer, Uncontrolled Resource Consumption

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to disclose information, cause a denial-of-service (DoS) condition, or execute arbitrary code.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Siemens products, are affected:

  • Siemens ST7 ScadaConnect (6NH7997-5DA10-0AA0): Versions prior to 1.1

3.2 Vulnerability Overview

3.2.1 INTEGER OVERFLOW OR WRAPAROUND CWE-190

An issue was discovered in libxml2 before 2.10.3. When parsing a multi-gigabyte XML document with the XML_PARSE_HUGE parser option enabled, several integer counters can overflow. This results in an attempt to access an array at a negative 2GB offset, typically leading to a segmentation fault.

CVE-2022-40303 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.2 DOUBLE FREE CWE-415

An issue was discovered in libxml2 before 2.10.3. Certain invalid XML entity definitions can corrupt a hash table key, potentially leading to subsequent logic errors. In one case, a double-free can be provoked.

CVE-2022-40304 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.3 IMPROPER CERTIFICATE VALIDATION CWE-295

A security vulnerability has been identified in all supported versions of OpenSSL related to the verification of X.509 certificate chains that include policy constraints. Attackers may be able to exploit this vulnerability by creating a malicious certificate chain that triggers exponential use of computational resources, leading to a denial-of-service (DoS) attack on affected systems. Policy processing is disabled by default but can be enabled by passing the -policy argument to the command line utilities or by calling the X509_VERIFY_PARAM_set1_policies() function.

CVE-2023-0464 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.4 IMPROPER CERTIFICATE VALIDATION CWE-295

Applications that use a non-default option when verifying certificates may be vulnerable to an attack from a malicious CA to circumvent certain checks. Invalid certificate policies in leaf certificates are silently ignored by OpenSSL and other certificate policy checks are skipped for that certificate. A malicious CA could use this to deliberately assert invalid certificate policies in order to circumvent policy checking on the certificate altogether. Policy processing is disabled by default but can be enabled by passing the -policy argument to the command line utilities or by calling the X509_VERIFY_PARAM_set1_policies() function.

CVE-2023-0465 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N).

3.2.5 IMPROPER CERTIFICATE VALIDATION CWE-295

The function X509_VERIFY_PARAM_add0_policy() is documented to implicitly enable the certificate policy check when doing certificate verification. However the implementation of the function does not enable the check which allows certificates with invalid or incorrect policies to pass the certificate verification.As suddenly enabling the policy check could break existing deployments it was decided to keep the existing behavior of the X509_VERIFY_PARAM_add0_policy()function.Instead the applications that require OpenSSL to perform certificate policy check need to use X509_VERIFY_PARAM_set1_policies() or explicitly enable the policy check by calling X509_VERIFY_PARAM_set_flags() with the X509_V_FLAG_POLICY_CHECK flag argument.Certificate policy checks are disabled by default in OpenSSL and are not commonly used by applications.

CVE-2023-0466 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N).

3.2.6 INEFFICIENT REGULAR EXPRESSION COMPLEXITY CWE-1333

Issue summary: Checking excessively long DH keys or parameters may be very slow. Impact summary: Applications that use the functions DH_check(), DH_check_ex() or EVP_PKEY_param_check() to check a DH key or DH parameters may experience long delays. Where the key or parameters that are being checked have been obtained from an untrusted source this may lead to a Denial-of-Service. The function DH_check() performs various checks on DH parameters. One of those checks confirms that the modulus ('p' parameter) is not too large. Trying to use a very large modulus is slow and OpenSSL will not normally use a modulus which is over 10,000 bits in length. However the DH_check() function checks numerous aspects of the key or parameters that have been supplied. Some of those checks use the supplied modulus value even if it has already been found to be too large. An application that calls DH_check() and supplies a key or parameters obtained from an untrusted source could be vulnerable to a Denial-of-Service attack. The function DH_check() is itself called by a number of other OpenSSL functions. An application calling any of those other functions may similarly be affected. The other functions affected by this are DH_check_ex() and EVP_PKEY_param_check(). Also vulnerable are the OpenSSL dhparam and pkeyparam command line applications when using the '-check' option. The OpenSSL SSL/TLS implementation is not affected by this issue. The OpenSSL 3.0 and 3.1 FIPS providers are not affected by this issue.

CVE-2023-3446 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L).

3.2.7 IMPROPER CHECK FOR UNUSUAL OR EXCEPTIONAL CONDITIONS CWE-754

Issue summary: Generating excessively long X9.42 DH keys or checking excessively long X9.42 DH keys or parameters may be very slow. Impact summary: Applications that use the functions DH_generate_key() to generate an X9.42 DH key may experience long delays. Likewise, applications that use DH_check_pub_key(), DH_check_pub_key_ex() or EVP_PKEY_public_check() to check an X9.42 DH key or X9.42 DH parameters may experience long delays. Where the key or parameters that are being checked have been obtained from an untrusted source this may lead to a Denial-of-Service. While DH_check() performs all the necessary checks (as of CVE-2023-3817), DH_check_pub_key() doesn't make any of these checks, and is therefore vulnerable for excessively large P and Q parameters. Likewise, while DH_generate_key() performs a check for an excessively large P, it doesn't check for an excessively large Q. An application that calls DH_generate_key() or DH_check_pub_key() and supplies a key or parameters obtained from an untrusted source could be vulnerable to a Denial-of-Service attack. DH_generate_key() and DH_check_pub_key() are also called by a number of other OpenSSL functions. An application calling any of those other functions may similarly be affected. The other functions affected by this are DH_check_pub_key_ex(), EVP_PKEY_public_check(), and EVP_PKEY_generate(). Also vulnerable are the OpenSSL pkey command line application when using the "-pubcheck" option, as well as the OpenSSL genpkey command line application. The OpenSSL SSL/TLS implementation is not affected by this issue. The OpenSSL 3.0 and 3.1 FIPS providers are not affected by this issue.

CVE-2023-5678 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L).

3.2.8 IMPROPER INPUT VALIDATION CWE-20

.NET and Visual Studio Remote Code Execution Vulnerability

CVE-2023-21808 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.9 IMPROPER INPUT VALIDATION CWE-20

.NET, .NET Framework, and Visual Studio Remote Code Execution Vulnerability

CVE-2023-24895 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.10 IMPROPER INPUT VALIDATION CWE-20

.NET, .NET Framework, and Visual Studio Remote Code Execution Vulnerability

CVE-2023-24897 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.11 IMPROPER INPUT VALIDATION CWE-20

.NET, .NET Framework, and Visual Studio Elevation of Privilege Vulnerability

CVE-2023-24936 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.12 IMPROPER INPUT VALIDATION CWE-20

.NET DLL Hijacking Remote Code Execution Vulnerability

CVE-2023-28260 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.13 NULL POINTER DEREFERENCE CWE-476

In libxml2 before 2.10.4, parsing of certain invalid XSD schemas can lead to a NULL pointer dereference and subsequently a segfault. This occurs in xmlSchemaFixupComplexType in xmlschemas.c.

CVE-2023-28484 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.14 IMPROPER INPUT VALIDATION CWE-20

.NET, .NET Framework, and Visual Studio Denial-of-Service Vulnerability

CVE-2023-29331 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.15 DOUBLE FREE CWE-415

An issue was discovered in libxml2 before 2.10.4. When hashing empty dict strings in a crafted XML document, xmlDictComputeFastKey in dict.c can produce non-deterministic values, leading to various logic and memory errors, such as a double free. This behavior occurs because there is an attempt to use the first byte of an empty string, and any value is possible (not solely the '\0' value).

CVE-2023-29469 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.16 IMPROPER INPUT VALIDATION CWE-20

.NET and Visual Studio Elevation of Privilege Vulnerability

CVE-2023-32032 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:U/C:L/I:H/A:H).

3.2.17 IMPROPER INPUT VALIDATION CWE-20

.NET and Visual Studio Remote Code Execution Vulnerability

CVE-2023-33126 has been assigned to this vulnerability. A CVSS v3 base score of 7.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H).

3.2.18 IMPROPER INPUT VALIDATION CWE-20

.NET and Visual Studio Elevation of Privilege Vulnerability

CVE-2023-33127 has been assigned to this vulnerability. A CVSS v3 base score of 8.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.19 IMPROPER INPUT VALIDATION CWE-20

.NET and Visual Studio Remote Code Execution Vulnerability

CVE-2023-33128 has been assigned to this vulnerability. A CVSS v3 base score of 7.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H).

3.2.20 IMPROPER INPUT VALIDATION CWE-20

.NET and Visual Studio Elevation of Privilege Vulnerability

CVE-2023-33135 has been assigned to this vulnerability. A CVSS v3 base score of 7.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H).

3.2.21 IMPROPER INPUT VALIDATION CWE-20

ASP.NET and Visual Studio Security Feature Bypass Vulnerability

CVE-2023-33170 has been assigned to this vulnerability. A CVSS v3 base score of 8.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.22 IMPROPER INPUT VALIDATION CWE-20

.NET and Visual Studio Remote Code Execution Vulnerability

CVE-2023-35390 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.23 IMPROPER INPUT VALIDATION CWE-20

ASP.NET Core SignalR and Visual Studio Information Disclosure Vulnerability

CVE-2023-35391 has been assigned to this vulnerability. A CVSS v3 base score of 6.2 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

3.2.24 IMPROPER INPUT VALIDATION CWE-20

ASP.NET Core Denial-of-Service Vulnerability

CVE-2023-36038 has been assigned to this vulnerability. A CVSS v3 base score of 8.2 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:H).

3.2.25 IMPROPER INPUT VALIDATION CWE-20

.NET, .NET Framework, and Visual Studio Elevation of Privilege Vulnerability

CVE-2023-36049 has been assigned to this vulnerability. A CVSS v3 base score of 7.6 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:H/A:L).

3.2.26 IMPROPER INPUT VALIDATION CWE-20

Microsoft QUIC Denial-of-Service Vulnerability

CVE-2023-36435 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.27 IMPROPER INPUT VALIDATION CWE-20

ASP.NET Core - Security Feature Bypass Vulnerability

CVE-2023-36558 has been assigned to this vulnerability. A CVSS v3 base score of 6.2 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

3.2.28 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

Visual Studio Remote Code Execution Vulnerability

CVE-2023-36792 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.29 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

Visual Studio Remote Code Execution Vulnerability

CVE-2023-36793 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.30 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

Visual Studio Remote Code Execution Vulnerability

CVE-2023-36794 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.31 MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

Visual Studio Remote Code Execution Vulnerability

CVE-2023-36796 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.32 IMPROPER INPUT VALIDATION CWE-20

.NET Core and Visual Studio Denial-of-Service Vulnerability

CVE-2023-36799 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.33 IMPROPER INPUT VALIDATION CWE-20

Microsoft QUIC Denial-of-Service Vulnerability

CVE-2023-38171 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.34 IMPROPER INPUT VALIDATION CWE-20

.NET Core and Visual Studio Denial-of-Service Vulnerability

CVE-2023-38178 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.35 IMPROPER INPUT VALIDATION CWE-20

.NET and Visual Studio Denial-of-Service Vulnerability

CVE-2023-38180 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.36 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

Xmlsoft Libxml2 v2.11.0 was discovered to contain an out-of-bounds read via the xmlSAX2StartElement() function at /libxml2/SAX2.c. This vulnerability allows attackers to cause a Denial-of-Service (DoS) via supplying a crafted XML file. NOTE: the vendor's position is that the product does not support the legacy SAX1 interface with custom callbacks; there is a crash even without crafted input.

CVE-2023-39615 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.37 UNCONTROLLED RESOURCE CONSUMPTION CWE-400

The HTTP/2 protocol allows a denial-of-service (server resource consumption) because request cancellation can reset many streams quickly, as exploited in the wild in August through October 2023.

CVE-2023-44487 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities, Energy, Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • ST7 ScadaConnect (6NH7997-5DA10-0AA0): Update to V1.1 or later version.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-341067 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • June 13, 2024: Initial Publication

Siemens PowerSys

By: CISA
13 June 2024 at 08:00

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). 

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.5
  • ATTENTION: Low Attack Complexity
  • Vendor: Siemens
  • Equipment: PowerSys
  • Vulnerability: Improper Authentication

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow a local attacker to bypass authentication, thereby gaining administrative privileges for the managed remote devices.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following products of Siemens are affected:

  • Siemens PowerSys: versions prior to V3.11

3.2 Vulnerability Overview

3.2.1 IMPROPER AUTHENTICATION CWE-287

Siemens PowerSys insufficiently protects responses to authentication requests. This could allow a local attacker to bypass authentication, thereby gaining administrative privileges for the managed remote devices.

CVE-2024-36266 has been assigned to this vulnerability. A CVSS v3 base score of 9.3 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-36266. A base score of 8.5 has been calculated; the CVSS vector string is (AV:L/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:N/SC:H/SI:H/SA:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Turek Witold from Polskie Sieci Elektroenergetyczne reported this vulnerability to Siemens.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-024584 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely.

5. UPDATE HISTORY

  • June 13, 2024: Initial Publication

Siemens SIMATIC and SIPLUS

By: CISA
13 June 2024 at 08:00

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). 

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 9.8
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: SIMATIC, SIPLUS
  • Vulnerabilities: Inadequate Encryption Strength, Improper Restriction of Operations within the Bounds of a Memory Buffer, Race Condition, Injection, Double Free, Integer Overflow or Wraparound, Improper Locking, NULL Pointer Dereference, Use-After-Free, Improper Input Validation, Improper Certificate Validation, Missing Release of Memory after Effective Lifetime, Out-of-bounds Read, Infinite Loop

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to leak memory, create a denial-of-service condition, or execute arbitrary code.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following products of Siemens, are affected:

  • Siemens SIMATIC CP 1542SP-1 (6GK7542-6UX00-0XE0): All versions prior to V2.3
  • Siemens SIMATIC CP 1542SP-1 IRC (6GK7542-6VX00-0XE0): All versions prior to V2.3
  • Siemens SIMATIC CP 1543SP-1 (6GK7543-6WX00-0XE0): All versions prior to V2.3
  • Siemens SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (6AG2542-6VX00-4XE0): All versions prior to V2.3
  • Siemens SIPLUS ET 200SP CP 1543SP-1 ISEC (6AG1543-6WX00-7XE0): All versions prior to V2.3
  • Siemens SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (6AG2543-6WX00-4XE0): All versions prior to V2.3

3.2 Vulnerability Overview

3.2.1 INADEQUATE ENCRYPTION STRENGTH CWE-326

AES OCB mode for 32-bit x86 platforms using the AES-NI assembly optimised implementation will not encrypt the entirety of the data under some circumstances. This could reveal sixteen bytes of data that was preexisting in the memory that wasn't written. In the special case of "in place" encryption, sixteen bytes of the plaintext would be revealed. Since OpenSSL does not support OCB based cipher suites for TLS and DTLS, they are both unaffected.

CVE-2022-2097 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).

3.2.2 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

A vulnerability classified as problematic has been found in Linux Kernel. This affects the function fib_nh_match of the file net/ipv4/fib_semantics.c of the component IPv4 Handler. The manipulation leads to out-of-bounds read. It is possible to initiate the attack remotely. It is recommended to apply a patch to fix this issue. The identifier VDB-210357 was assigned to this vulnerability.

CVE-2022-3435 has been assigned to this vulnerability. A CVSS v3 base score of 4.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:N/A:N).

3.2.3 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

A vulnerability has been found in Linux Kernel and classified as critical. Affected by this vulnerability is the function area_cache_get of the file drivers/net/ethernet/netronome/nfp/nfpcore/nfp_cppcore.c of the component IPsec. The manipulation leads to use after free. It is recommended to apply a patch to fix this issue. The identifier VDB-211045 was assigned to this vulnerability.

CVE-2022-3545 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.4 CONCURRENT EXECUTION USING SHARED RESOURCE WITH IMPROPER SYNCHRONIZATION ('RACE CONDITION') CWE-362

A vulnerability was found in Linux Kernel. It has been declared as problematic. Affected by this vulnerability is the function follow_page_pte of the file mm/gup.c of the component BPF. The manipulation leads to race condition. The attack can be launched remotely. It is recommended to apply a patch to fix this issue. The identifier VDB-211921 was assigned to this vulnerability.

CVE-2022-3623 has been assigned to this vulnerability. A CVSS v3 base score of 5.0 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:L/UI:N/S:U/C:L/I:L/A:L).

3.2.5 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS IN OUTPUT USED BY A DOWNSTREAM COMPONENT ('INJECTION') CWE-74

Guests can trigger NIC interface reset/abort/crash via netback It is possible for a guest to trigger a NIC interface reset/abort/crash in a Linux based network backend by sending certain kinds of packets. It appears to be an (unwritten?) assumption in the rest of the Linux network stack that packet protocol headers are all contained within the linear section of the SKB and some NICs behave badly if this is not the case. This has been reported to occur with Cisco (enic) and Broadcom NetXtrem II BCM5780 (bnx2x) though it may be an issue with other NICs/drivers as well. In case the frontend is sending requests with split headers, netback will forward those violating above mentioned assumption to the networking core, resulting in said misbehavior.

CVE-2022-3643 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:C/C:N/I:N/A:H).

3.2.6 INADEQUATE ENCRYPTION STRENGTH CWE-326

A timing based side channel exists in the OpenSSL RSA Decryption implementation which could be sufficient to recover a plaintext across a network in a Bleichenbacher style attack. To achieve a successful decryption an attacker would have to be able to send a very large number of trial messages for decryption. The vulnerability affects all RSA padding modes: PKCS#1 v1.5, RSA-OEAP and RSASVE. For example, in a TLS connection, RSA is commonly used by a client to send an encrypted pre-master secret to the server. An attacker that had observed a genuine connection between a client and a server could use this flaw to send trial messages to the server and record the time taken to process them. After a sufficiently large number of messages the attacker could recover the pre-master secret used for the original connection and thus be able to decrypt the application data sent over that connection.

CVE-2022-4304 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:N).

3.2.7 DOUBLE FREE CWE-415

The function PEM_read_bio_ex() reads a PEM file from a BIO and parses and decodes the "name" (e.g. "CERTIFICATE"), any header data and the payload data. If the function succeeds then the "name_out", "header" and "data" arguments are populated with pointers to buffers containing the relevant decoded data. The caller is responsible for freeing those buffers. It is possible to construct a PEM file that results in 0 bytes of payload data. In this case PEM_read_bio_ex() will return a failure code but will populate the header argument with a pointer to a buffer that has already been freed. If the caller also frees this buffer then a double free will occur. This will most likely lead to a crash. This could be exploited by an attacker who has the ability to supply malicious PEM files for parsing to achieve a denial-of-service attack. The functions PEM_read_bio() and PEM_read() are simple wrappers around PEM_read_bio_ex() and therefore these functions are also directly affected. These functions are also called indirectly by a number of other OpenSSL functions including PEM_X509_INFO_read_bio_ex() and SSL_CTX_use_serverinfo_file() which are also vulnerable. Some OpenSSL internal uses of these functions are not vulnerable because the caller does not free the header argument if PEM_read_bio_ex() returns a failure code. These locations include the PEM_read_bio_TYPE() functions as well as the decoders introduced in OpenSSL 3.0. The OpenSSL asn1parse command line application is also impacted by this issue.

CVE-2022-4450 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.8 INTEGER OVERFLOW OR WRAPAROUND CWE-190

An issue was discovered in libxml2 before 2.10.3. When parsing a multi-gigabyte XML document with the XML_PARSE_HUGE parser option enabled, several integer counters can overflow. This results in an attempt to access an array at a negative 2GB offset, typically leading to a segmentation fault.

CVE-2022-40303 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.9 DOUBLE FREE CWE-415

An issue was discovered in libxml2 before 2.10.3. Certain invalid XML entity definitions can corrupt a hash table key, potentially leading to subsequent logic errors. In one case, a double-free can be provoked.

CVE-2022-40304 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.10 IMPROPER LOCKING CWE-667

Guests can trigger deadlock in Linux netback driver [This CNA information record relates to multiple CVEs; the text explains which aspects/vulnerabilities correspond to which CVE.] The patch for XSA-392 introduced another issue which might result in a deadlock when trying to free the SKB of a packet dropped due to the XSA-392 handling (CVE-2022-42328). Additionally when dropping packages for other reasons the same deadlock could occur in case of netpoll being active for the interface the xen-netback driver is connected to (CVE-2022-42329).

CVE-2022-42328 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.11 IMPROPER LOCKING CWE-667

Guests can trigger deadlock in Linux netback drive. The patch for XSA-392 introduced another issue which might result in a deadlock when trying to free the SKB of a packet dropped due to the XSA-392 handling (CVE-2022-42328). Additionally when dropping packages for other reasons the same deadlock could occur in case of netpoll being active for the interface the xen-netback driver is connected to (CVE-2022-42329).

CVE-2022-42329 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.12 NULL POINTER DEREFERENCE CWE-476

handle_ipDefaultTTL in agent/mibgroup/ip-mib/ip_scalars.c in Net-SNMP 5.8 through 5.9.3 has a NULL Pointer Exception bug that can be used by a remote attacker (who has write access) to cause the instance to crash via a crafted UDP packet, resulting in Denial-of-Service.

CVE-2022-44792 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.13 NULL POINTER DEREFERENCE CWE-476

handle_ipv6IpForwarding in agent/mibgroup/ip-mib/ip_scalars.c in Net-SNMP 5.4.3 through 5.9.3 has a NULL Pointer Exception bug that can be used by a remote attacker to cause the instance to crash via a crafted UDP packet, resulting in Denial of Service.

CVE-2022-44793 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.14 USE AFTER FREE CWE-416

The public API function BIO_new_NDEF is a helper function used for streaming ASN.1 data via a BIO. It is primarily used internally to OpenSSL to support the SMIME, CMS and PKCS7 streaming capabilities, but may also be called directly by end user applications. The function receives a BIO from the caller, prepends a new BIO_f_asn1 filter BIO onto the front of it to form a BIO chain, and then returns the new head of the BIO chain to the caller. Under certain conditions, for example if a CMS recipient public key is invalid, the new filter BIO is freed and the function returns a NULL result indicating a failure. However, in this case, the BIO chain is not properly cleaned up and the BIO passed by the caller still retains internal pointers to the previously freed filter BIO. If the caller then goes on to call BIO_pop() on the BIO then a use-after-free will occur. This will most likely result in a crash. This scenario occurs directly in the internal function B64_write_ASN1() which may cause BIO_new_NDEF() to be called and will subsequently call BIO_pop() on the BIO. This internal function is in turn called by the public API functions PEM_write_bio_ASN1_stream, PEM_write_bio_CMS_stream, PEM_write_bio_PKCS7_stream, SMIME_write_ASN1, SMIME_write_CMS and SMIME_write_PKCS7. Other public API functions that may be impacted by this include i2d_ASN1_bio_stream, BIO_new_CMS, BIO_new_PKCS7, i2d_CMS_bio_stream and i2d_PKCS7_bio_stream. The OpenSSL cms and smime command line applications are similarly affected.

CVE-2023-0215 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.15 IMPROPER INPUT VALIDATION CWE-20

There is a type confusion vulnerability relating to X.400 address processing inside an X.509 GeneralName. X.400 addresses were parsed as an ASN1_STRING but the public structure definition for GENERAL_NAME incorrectly specified the type of the x400Address field as ASN1_TYPE. This field is subsequently interpreted by the OpenSSL function GENERAL_NAME_cmp as an ASN1_TYPE rather than an ASN1_STRING. When CRL checking is enabled (i.e. the application sets the X509_V_FLAG_CRL_CHECK flag), this vulnerability may allow an attacker to pass arbitrary pointers to a memcmp call, enabling them to read memory contents or enact a denial-of-service. In most cases, the attack requires the attacker to provide both the certificate chain and CRL, neither of which need to have a valid signature. If the attacker only controls one of these inputs, the other input must already contain an X.400 address as a CRL distribution point, which is uncommon. As such, this vulnerability is most likely to only affect applications which have implemented their own functionality for retrieving CRLs over a network.

CVE-2023-0286 has been assigned to this vulnerability. A CVSS v3 base score of 7.4 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:H).

3.2.16 IMPROPER CERTIFICATE VALIDATION CWE-295

A security vulnerability has been identified in all supported versions of OpenSSL related to the verification of X.509 certificate chains that include policy constraints. Attackers may be able to exploit this vulnerability by creating a malicious certificate chain that triggers exponential use of computational resources, leading to a denial-of-service (DoS) attack on affected systems. Policy processing is disabled by default but can be enabled by passing the -policy argument to the command line utilities or by calling the X509_VERIFY_PARAM_set1_policies() function.

CVE-2023-0464 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.17 IMPROPER CERTIFICATE VALIDATION CWE-295

Applications that use a non-default option when verifying certificates may be vulnerable to an attack from a malicious CA to circumvent certain checks. Invalid certificate policies in leaf certificates are silently ignored by OpenSSL and other certificate policy checks are skipped for that certificate. A malicious CA could use this to deliberately assert invalid certificate policies in order to circumvent policy checking on the certificate altogether. Policy processing is disabled by default but can be enabled by passing the -policy argument to the command line utilities or by calling the X509_VERIFY_PARAM_set1_policies() function.

CVE-2023-0465 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N).

3.2.18 IMPROPER CERTIFICATE VALIDATION CWE-295

The function X509_VERIFY_PARAM_add0_policy() is documented to implicitly enable the certificate policy check when doing certificate verification. However the implementation of the function does notenable the check which allows certificates with invalid or incorrect policies to pass the certificate verification.As suddenly enabling the policy check could break existing deployments it was decided to keep the existing behavior of the X509_VERIFY_PARAM_add0_policy()function.Instead the applications that require OpenSSL to perform certificate policy check need to use X509_VERIFY_PARAM_set1_policies() or explicitly enable the policy check by calling X509_VERIFY_PARAM_set_flags() withthe X509_V_FLAG_POLICY_CHECK flag argument.Certificate policy checks are disabled by default in OpenSSL and are not commonly used by applications.

CVE-2023-0466 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N).

3.2.19 NULL POINTER DEREFERENCE CWE-476

In libxml2 before 2.10.4, parsing of certain invalid XSD schemas can lead to a NULL pointer dereference and subsequently a segfault. This occurs in xmlSchemaFixupComplexType in xmlschemas.c.

CVE-2023-28484 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.20 DOUBLE FREE CWE-415

An issue was discovered in libxml2 before 2.10.4. When hashing empty dict strings in a crafted XML document, xmlDictComputeFastKey in dict.c can produce non-deterministic values, leading to various logic and memory errors, such as a double free. This behavior occurs because there is an attempt to use the first byte of an empty string, and any value is possible (not solely the '\0' value).

CVE-2023-29469 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H).

3.2.21 MISSING RELEASE OF MEMORY AFTER EFFECTIVE LIFETIME CWE-401

The webserver implementation of the affected products does not correctly release allocated memory after it has been used. An attacker with network access could use this vulnerability to cause a denial-of-service condition in the webserver of the affected product.

CVE-2023-38380 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2024-38380. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).

3.2.22 OUT-OF-BOUNDS READ CWE-125

An issue was discovered in lldpd before 1.0.17. By crafting a CDP PDU packet with specific CDP_TLV_ADDRESSES TLVs, a malicious actor can remotely force the lldpd daemon to perform an out-of-bounds read on heap memory. This occurs in cdp_decode in daemon/protocols/cdp.c.

CVE-2023-41910 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.23 LOOP WITH UNREACHABLE EXIT CONDITION ('INFINITE LOOP') CWE-835

The web server of affected products, if configured to allow the import of PKCS12 containers, could end up in an infinite loop when processing incomplete certificate chains. This could allow an authenticated remote attacker to create a denial of service condition by importing specially crafted PKCS12 containers.

CVE-2023-50763 has been assigned to this vulnerability. A CVSS v3 base score of 4.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2023-50763. A base score of 6.9 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Chemical, Critical Manufacturing, Energy, Transportation, and Water and Wastewater Systems.
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

Update to V2.3 or latest version.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-625862 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • June 13, 2024: Initial Publication

Siemens SINEC Traffic Analyzer

By: CISA
13 June 2024 at 08:00

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). 

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.7
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: SINEC Traffic Analyzer
  • Vulnerabilities: Out-of-bounds Write, Insufficient Session Expiration, Cross-Site Request Forgery (CSRF), Insufficiently Protected Credentials, Exposed Dangerous Method or Function, Cleartext Transmission of Sensitive Information, Sensitive Cookie in HTTPS Session Without 'Secure' Attribute, Improper Input Validation

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to cause a denial-of-service condition, disclose sensitive information, or modify files.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following products of Siemens, are affected:

  • SINEC Traffic Analyzer (6GK8822-1BG01-0BA0): Versions prior to V1.2

3.2 Vulnerability Overview

3.2.1 OUT-OF-BOUNDS WRITE CWE-787

NGINX Open Source before versions 1.23.2 and 1.22.1, NGINX Open Source Subscription before versions R2 P1 and R1 P1, and NGINX Plus before versions R27 P1 and R26 P1 have a vulnerability in the module ngx_http_mp4_module that might allow a local attacker to cause a worker process crash, or might result in worker process memory disclosure by using a specially crafted audio or video file. The issue affects only NGINX products that are built with the module ngx_http_mp4_module, when the mp4 directive is used in the configuration file. Further, the attack is possible only if an attacker can trigger processing of a specially crafted audio or video file with the module ngx_http_mp4_module.

CVE-2022-41742 has been assigned to this vulnerability. A CVSS v3 base score of 7.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:H).

3.2.2 INSUFFICIENT SESSION EXPIRATION CWE-613

The affected application does not expire the session. This could allow an attacker to get unauthorized access.

CVE-2024-35206 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-35206. A base score of 8.6 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:P/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N)

3.2.3 CROSS-SITE REQUEST FORGERY (CSRF) CWE-352

The web interface of the affected devices are vulnerable to Cross-Site Request Forgery (CSRF) attacks. By tricking an authenticated victim user to click a malicious link, an attacker could perform arbitrary actions on the device on behalf of the victim user.

CVE-2024-35207 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-35207. A base score of 8.5 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N)

3.2.4 INSUFFICIENTLY PROTECTED CREDENTIALS CWE-522

The affected web server stored the password in cleartext. This could allow attacker in a privileged position to obtain access passwords.

CVE-2024-35208 has been assigned to this vulnerability. A CVSS v3 base score of 6.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:C/C:L/I:L/A:L).

A CVSS v4 score has also been calculated for CVE-2024-35208. A base score of 4.8 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:L/VI:L/VA:L/SC:L/SI:L/SA:L)

3.2.5 EXPOSED DANGEROUS METHOD OR FUNCTION CWE-749

The affected web server is allowing HTTP methods like PUT and DELETE. This could allow an attacker to modify unauthorized files.

CVE-2024-35209 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N).

A CVSS v4 score has also been calculated for CVE-2024-35209. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N)

3.2.6 CLEARTEXT TRANSMISSION OF SENSITIVE INFORMATION CWE-319

The affected web server is not enforcing HSTS. This could allow an attacker to perform downgrade attacks exposing confidential information.

CVE-2024-35210 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:N).

A CVSS v4 score has also been calculated for CVE-2024-35210. A base score of 6.9 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:L/VI:L/VA:N/SC:N/SI:N/SA:N)

3.2.7 SENSITIVE COOKIE IN HTTPS SESSION WITHOUT 'SECURE' ATTRIBUTE CWE-614

The affected web server, after a successful login, sets the session cookie on the browser, without applying any security attributes (such as "Secure", "HttpOnly", or "SameSite").

CVE-2024-35211 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2024-35211. A base score of 7.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N)

3.2.8 IMPROPER INPUT VALIDATION CWE-20

The affected application lacks input validation due to which an attacker can gain access to the Database entries.

CVE-2024-35212 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2024-35212. A base score of 7.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:P/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N)

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Energy
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • SINEC Traffic Analyzer (6GK8822-1BG01-0BA0): Update to V1.2 or later version

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-196737 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • June 13, 2024: Initial Publication

Rockwell Automation FactoryTalk View SE

By: CISA
13 June 2024 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.5
  • ATTENTION: Low attack complexity
  • Vendor: Rockwell Automation
  • Equipment: FactoryTalk View SE
  • Vulnerability: Incorrect Permission Assignment for Critical Resource

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow low-privilege users to edit scripts, bypassing access control lists, and potentially gain further access within the system.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Rockwell Automation reports that the following versions of FactoryTalk Software are affected:

  • FactoryTalk View SE: v12.0

3.2 Vulnerability Overview

3.2.1 Incorrect Permission Assignment for Critical Resource CWE-732

A privilege escalation vulnerability exists in FactoryTalk View SE. The vulnerability allows low-privilege users to edit scripts, bypassing Access Control Lists, and potentially gaining further access within the system.

CVE-2024-37369 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-37369. A base score of 8.5 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N ).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Rockwell Automation reported this vulnerability to CISA.

4. MITIGATIONS

Rockwell Automation has corrected this problem in V14.0 and later

Rockwell Automation encourages users of the affected software, who are not able to upgrade to one of the corrected versions, to apply the risk mitigations where possible.

For more information, see Rockwell Automation's security advisory

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • June 13, 2024: Initial Publication

CISA Releases Twenty Industrial Control Systems Advisories

By: CISA
13 June 2024 at 08:00

CISA released twenty Industrial Control Systems (ICS) advisories on June 13, 2024. These advisories provide timely information about current security issues, vulnerabilities, and exploits surrounding ICS.

CISA encourages users and administrators to review the newly released ICS advisories for technical details and mitigations.

Siemens SIMATIC S7-200 SMART Devices

By: CISA
13 June 2024 at 08:00

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). 

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.8
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: SIMATIC S7-200 SMART devices
  • Vulnerability: Use of Insufficiently Random Values

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to create a denial-of-service condition.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Siemens programmable logic controllers are affected:

  • Siemens SIMATIC S7-200 SMART CPU CR40 (6ES7288-1CR40-0AA0): All versions
  • Siemens SIMATIC S7-200 SMART CPU CR60 (6ES7288-1CR60-0AA0): All versions
  • Siemens SIMATIC S7-200 SMART CPU SR20 (6ES7288-1SR20-0AA0): All versions
  • Siemens SIMATIC S7-200 SMART CPU SR20 (6ES7288-1SR20-0AA1): All versions
  • Siemens SIMATIC S7-200 SMART CPU SR30 (6ES7288-1SR30-0AA0): All versions
  • Siemens SIMATIC S7-200 SMART CPU SR30 (6ES7288-1SR30-0AA1): All versions
  • Siemens SIMATIC S7-200 SMART CPU SR40 (6ES7288-1SR40-0AA0): All versions
  • Siemens SIMATIC S7-200 SMART CPU SR40 (6ES7288-1SR40-0AA1): All versions
  • Siemens SIMATIC S7-200 SMART CPU SR60 (6ES7288-1SR60-0AA0): All versions
  • Siemens SIMATIC S7-200 SMART CPU SR60 (6ES7288-1SR60-0AA1): All versions
  • Siemens SIMATIC S7-200 SMART CPU ST20 (6ES7288-1ST20-0AA0): All versions
  • Siemens SIMATIC S7-200 SMART CPU ST20 (6ES7288-1ST20-0AA1): All versions
  • Siemens SIMATIC S7-200 SMART CPU ST30 (6ES7288-1ST30-0AA0): All versions
  • Siemens SIMATIC S7-200 SMART CPU ST30 (6ES7288-1ST30-0AA1): All versions
  • Siemens SIMATIC S7-200 SMART CPU ST40 (6ES7288-1ST40-0AA0): All versions
  • Siemens SIMATIC S7-200 SMART CPU ST40 (6ES7288-1ST40-0AA1): All versions
  • Siemens SIMATIC S7-200 SMART CPU ST60 (6ES7288-1ST60-0AA0): All versions
  • Siemens SIMATIC S7-200 SMART CPU ST60 (6ES7288-1ST60-0AA1): All versions

3.2 Vulnerability Overview

3.2.1 USE OF INSUFFICIENTLY RANDOM VALUES CWE-330

Affected devices are using a predictable IP ID sequence number. This leaves the system susceptible to a family of attacks which rely on the use of predictable IP ID sequence numbers as their base method of attack and eventually could allow an attacker to create a denial-of-service condition.

CVE-2024-35292 has been assigned to this vulnerability. A CVSS v3 base score of 8.2 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2024-35292. A base score of 8.8 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:L/VI:N/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Chemical, Critical Manufacturing, Energy, Food and Agriculture, Water and Wastewater Systems
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported this vulnerability to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • Restrict access to the network where the affected products are located by introducing strict access control mechanisms.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-481506 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • June 13, 2024: Initial Publication

Siemens SITOP UPS1600

By: CISA
13 June 2024 at 08:00

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). 

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 5.6
  • ATTENTION: Exploitable remotely
  • Vendor: Siemens
  • Equipment: SITOP UPS1600 10 A Ethernet/ PROFINET (6EP4134-3AB00-2AY0), SITOP UPS1600 20 A Ethernet/ PROFINET (6EP4136-3AB00-2AY0), SITOP UPS1600 40 A Ethernet/ PROFINET (6EP4137-3AB00-2AY0), SITOP UPS1600 EX 20 A Ethernet PROFINET (6EP4136-3AC00-2AY0)
  • Vulnerabilities: Out-of-bounds Write

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to cause limited impact in the affected systems.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Siemens SITOP UPS1600, an uninterruptible power supply, are affected:

  • SITOP UPS1600 10 A Ethernet/ PROFINET (6EP4134-3AB00-2AY0): All versions prior to V2.5.4
  • SITOP UPS1600 20 A Ethernet/ PROFINET (6EP4136-3AB00-2AY0): All versions prior to V2.5.4
  • SITOP UPS1600 40 A Ethernet/ PROFINET (6EP4137-3AB00-2AY0): All versions prior to V2.5.4
  • SITOP UPS1600 EX 20 A Ethernet PROFINET (6EP4136-3AC00-2AY0) All versions prior to V2.5.4

3.2 Vulnerability Overview

3.2.1 OUT-OF-BOUNDS WRITE CWE-787

mstolfp in libntp/mstolfp.c in NTP 4.2.8p15 has an out-of-bounds write when adding a decimal point. An adversary may be able to attack a client ntpq process, but cannot attack ntpd.

CVE-2023-26552 has been assigned to this vulnerability. A CVSS v3.1 base score of 5.6 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:L/A:L).

3.2.2 OUT-OF-BOUNDS WRITE CWE-787

mstolfp in libntp/mstolfp.c in NTP 4.2.8p15 has an out-of-bounds write when copying the trailing number. An adversary may be able to attack a client ntpq process, but cannot attack ntpd.

CVE-2023-26553 has been assigned to this vulnerability. A CVSS v3.1 base score of 5.6 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:L/A:L).

3.2.3 OUT-OF-BOUNDS WRITE CWE-787

mstolfp in libntp/mstolfp.c in NTP 4.2.8p15 has an out-of-bounds write when adding a ‘\0' character. An adversary may be able to attack a client ntpq process, but cannot attack ntpd.

CVE-2023-26554 has been assigned to this vulnerability. A CVSS v3.1 base score of 5.6 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:L/A:L).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens recommends users to update to the latest version:

  • SITOP UPS1600 10 A Ethernet/ PROFINET (6EP4134-3AB00-2AY0): Update to V2.5.4 or later version
  • SITOP UPS1600 20 A Ethernet/ PROFINET (6EP4136-3AB00-2AY0): Update to V2.5.4 or later version
  • SITOP UPS1600 40 A Ethernet/ PROFINET (6EP4137-3AB00-2AY0): Update to V2.5.4 or later version
  • SITOP UPS1600 EX 20 A Ethernet PROFINET (6EP4136-3AC00-2AY0): Update to V2.5.4 or later version

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-238730 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. These vulnerabilities have a high attack complexity.

5. UPDATE HISTORY

  • June 13, 2024: Initial Publication

Phone Scammers Impersonating CISA Employees

By: CISA
12 June 2024 at 08:00

Impersonation scams are on the rise and often use the names and titles of government employees. The Cybersecurity and Infrastructure Security Agency (CISA) is aware of recent impersonation scammers claiming to represent the agency. As a reminder, CISA staff will never contact you with a request to wire money, cash, cryptocurrency, or use gift cards and will never instruct you to keep the discussion secret.

If you suspect you are a target of an impersonation scammer claiming to be a CISA employee: 
•    Do not pay the caller.
•    Take note of the phone number calling you.
•    Hang up immediately.
•    Validate the contact by calling CISA at (844) SAY-CISA (844-729-2472) or report it to law enforcement.
 

CISA Adds Two Known Exploited Vulnerabilities to Catalog

By: CISA
12 June 2024 at 08:00

CISA has added two new vulnerabilities to its Known Exploited Vulnerabilities Catalog, based on evidence of active exploitation.

These types of vulnerabilities are frequent attack vectors for malicious cyber actors and pose significant risks to the federal enterprise.

Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the Known Exploited Vulnerabilities Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information.

Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria.

Fortinet Releases Security Updates for FortiOS 

By: CISA
11 June 2024 at 08:00

Fortinet has released security updates to address a vulnerability in FortiOS. A cyber threat actor could exploit this vulnerability to take control of an affected system.   

Users and administrators are encouraged to review the following Fortinet Security Bulletin and apply the necessary updates:  

Microsoft Releases June 2024 Security Updates

By: CISA
11 June 2024 at 08:00

 Microsoft has released security updates to address vulnerabilities in multiple products. A cyber threat actor could exploit some of these vulnerabilities to take control of an affected system.  

Users and administrators are encouraged to review the following advisory and apply the necessary updates:  

AVEVA PI Asset Framework Client

By: CISA
11 June 2024 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 7.0
  • ATTENTION: Low attack complexity
  • Vendor: AVEVA
  • Equipment: PI Asset Framework Client
  • Vulnerability: Deserialization of Untrusted Data

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow malicious code execution.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of AVEVA PI Asset Framework Client, a tool to model either physical or logical objects, are affected:

  • PI Asset Framework Client: 2023
  • PI Asset Framework Client: 2018 SP3 P04 and prior

3.2 Vulnerability Overview

3.2.1 Deserialization of Untrusted Data CWE-502

There is a vulnerability in AVEVA PI Asset Framework Client that could allow malicious code to execute on the PI System Explorer environment under the privileges of an interactive user that was socially engineered to import XML supplied by an attacker.

CVE-2024-3467 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.3 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-3467. A base score of 7.0 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:N/PR:L/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United Kingdom

3.4 RESEARCHER

AVEVA reported this vulnerability to CISA.

4. MITIGATIONS

AVEVA recommends that organizations evaluate the impact of these vulnerabilities based on their operational environment, architecture, and product implementation. Customers using affected products should apply security updates as soon as possible:

  • (Recommended) All affected versions can be fixed by upgrading to PI AF Client 2023 Patch 1 or later:
    From OSI Soft Customer Portal, search for "Asset Framework" and select "PI Asset Framework (AF) Client 2023 Patch 1" or later.
  • (Alternative) AF Client 2018 SP3 P04 and prior can be fixed by deploying PI AF Client 2018 SP3 Patch 5 or later:
    From OSI Soft Customer Portal, search for "Asset Framework" and select either "PI Asset Framework (AF) Client 2018 SP3 Patch 5" or later.

AVEVA further recommends users follow general defensive measures:

  • Run PI System Explorer as a least privilege interactive account when possible.
  • Establish procedures for verifying the source of XML is trusted before importing into PI System Explorer.

For additional information please refer to AVEVA-2024-004

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely.

5. UPDATE HISTORY

  • June 11, 2024: Initial Publication

CISA Releases Six Industrial Control Systems Advisories

By: CISA
11 June 2024 at 08:00

CISA released six Industrial Control Systems (ICS) advisories on June 11, 2024. These advisories provide timely information about current security issues, vulnerabilities, and exploits surrounding ICS.

CISA encourages users and administrators to review the newly released ICS advisories for technical details and mitigations.

Rockwell Automation ControlLogix, GuardLogix, and CompactLogix

By: CISA
11 June 2024 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.3
  • ATTENTION: Low attack complexity
  • Vendor: Rockwell Automation
  • Equipment: ControlLogix, GuardLogix, CompactLogix
  • Vulnerability: Always-Incorrect Control Flow Implementation

2. RISK EVALUATION

Successful exploitation of this vulnerability could compromise the availability of the device.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Rockwell Automation reports that the following controllers are affected:

  • ControlLogix 5580: V34.011
  • GuardLogix 5580: V34.011
  • 1756-EN4: V4.001
  • CompactLogix 5380: V34.011
  • Compact GuardLogix 5380: V34.011
  • CompactLogix 5380: V34.011
  • ControlLogix 5580: V34.011
  • CompactLogix 5480: V34.011

3.2 Vulnerability Overview

3.2.1 Always-Incorrect Control Flow Implementation CWE-670

Rockwell Automation was made aware of a vulnerability that causes all affected controllers on the same network to result in a major nonrecoverable fault (MNRF/Assert). This vulnerability could be exploited by sending abnormal packets to the mDNS port. If exploited, the availability of the device would be compromised.

CVE-2024-5659 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.4 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2024-5659. A base score of 8.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Rockwell Automation reported this vulnerability to CISA.

4. MITIGATIONS

Rockwell Automation offers users the following solutions:

  • ControlLogix 5580: corrected in V34.014, V35.013, V36.011 and later
  • GuardLogix 5580: corrected in V34.014, V35.013, V36.011 and later
  • 1756-EN4: corrected in V6.001 and later
  • CompactLogix 5380: corrected in V34.014, V35.013, V36.011 and later
  • Compact GuardLogix 5380: corrected in V34.014, V35.013, V36.011 and later
  • CompactLogix 5380: corrected in V34.014, V35.013, V36.011 and later
  • ControlLogix 5580: corrected in V34.014, V35.013, V36.011 and later
  • CompactLogix 5480: corrected in V34.014, V35.013, V36.011 and later

Rockwell Automation encourages users of the affected software, who are not able to upgrade to one of the corrected versions, to apply the risk mitigations where possible.

For more information, see Rockwell Automation's security advisory

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • June 11, 2024: Initial Publication

Intrado 911 Emergency Gateway

By: CISA
11 June 2024 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 10.0
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Intrado
  • Equipment: 911 Emergency Gateway (EGW)
  • Vulnerability: SQL Injection

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to execute malicious code, exfiltrate data, or manipulate the database.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Intrado's 911 Emergency Gateway are affected:

  • 911 Emergency Gateway (EGW): All versions

3.2 Vulnerability Overview

3.2.1 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN SQL COMMAND ('SQL INJECTION') CWE-89

Intrado 911 Emergency Gateway login form is vulnerable to an unauthenticated blind time-based SQL injection, which may allow an attacker to execute malicious code, exfiltrate data, or manipulate the database.

CVE-2024-1839 has been assigned to this vulnerability. A CVSS v3.1 base score of 10.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-1839. A base score of 10.0 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:L/S:P/AU:Y/R:U/V:C).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Emergency Services
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

An anonymous individual reported this vulnerability to CISA.

4. MITIGATIONS

Intrado has provided a patch to mitigate the vulnerability. Any EGWs deployed on older revisions will need to be upgraded to the 5.5/5.6 branch to apply the patch. For assistance in obtaining the patch, contact Intrado's technical support group at 1-888-908-4167 or E911Support@intrado.com.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • June 11, 2024: Initial Publication

AVEVA PI Web API

By: CISA
11 June 2024 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.4
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: AVEVA
  • Equipment: PI Web API
  • Vulnerability: Deserialization of Untrusted Data

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to perform remote code execution.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of AVEVA PI Web API, a RESTful interface to the PI system, are affected:

  • AVEVA PI Web API: Versions 2023 and prior

3.2 Vulnerability Overview

3.2.1 Deserialization of Untrusted Data CWE-502

There is a vulnerability in AVEVA PI Web API that could allow malicious code to execute on the PI Web API environment under the privileges of an interactive user that was socially engineered to use API XML import functionality with content supplied by an attacker.

CVE-2024-3468 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.6 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:L).

A CVSS v4 score has also been calculated for CVE-2024-3468. A base score of 8.4 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:L/UI:A/VC:H/VI:H/VA:L/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United Kingdom

3.4 RESEARCHER

AVEVA reported this vulnerability to CISA.

4. MITIGATIONS

AVEVA recommends that organizations evaluate the impact of these vulnerabilities based on their operational environment, architecture, and product implementation. Customers using affected products should apply security updates as soon as possible:

From OSI Soft Customer Portal, search for "PI Web API" and select version "2023 SP1" or later.

(Alternative) PI Web API 2021 SP3 can be fixed by upgrading PI AF Client to one of the versions specified in AVEVA Security Bulletin AVEVA-2024-004 / ICSA-24-163-03

AVEVA further recommends users follow general defensive measures:

  • Set "DisableWrites" configuration setting to true, if this instance of PI Web API is used only for reading data or GET requests.
  • Uninstall Core Endpoints feature if this instance of PI Web API is used only for data collection from AVEVA Adapters. Keep OMF feature installed.
  • Limit AF Servers' Administrators, so that most of the PI Web API user accounts don't have the permission to change the backend AF servers.

For additional information please refer to AVEVA-2024-003

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • June 11, 2024: Initial Publication

MicroDicom DICOM Viewer

By: CISA
11 June 2024 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.7
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: MicroDicom
  • Equipment: DICOM Viewer
  • Vulnerabilities: Improper Authorization in Handler for Custom URL Scheme, Stack-based Buffer Overflow

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to both retrieve and plant medical image files on a victim's system and cause a stack-based buffer overflow, which could result in sensitive information disclosure and arbitrary code execution.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of MicroDicom DICOM Viewer, a medical image viewer, are affected:

  • DICOM Viewer: Versions prior to 2024.2

3.2 Vulnerability Overview

3.2.1 IMPROPER AUTHORIZATION IN HANDLER FOR CUSTOM URL SCHEME CWE-939

An attacker could retrieve sensitive files (medical images) as well as plant new medical images or overwrite existing medical images on a victim's system. User interaction is required to exploit this vulnerability.

CVE-2024-33606 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-33606. A base score of 8.6 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.2 STACK-BASED BUFFER OVERFLOW CWE-121

The affected product is vulnerable to a stack-based buffer overflow, which may allow an attacker to execute arbitrary code on affected installations of DICOM Viewer. User interaction is required to exploit this vulnerability.

CVE-2024-28877 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-28877. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Healthcare and Public Health
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Bulgaria

3.4 RESEARCHER

Michael Heinzl reported these vulnerabilities to CISA.

4. MITIGATIONS

MicroDicom recommends users upgrade to DICOM Viewer version 2024.2.

CISA recommends users take defensive measures to minimize the risk of exploitation of this these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • June 11, 2024: Initial Publication

Emerson Ovation

By: CISA
6 June 2024 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 9.8
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Emerson
  • Equipment: Ovation
  • Vulnerabilities: Missing Authentication for Critical Function, Insufficient Verification of Data Authenticity

CISA is aware of a public report, known as "OT:ICEFALL", detailing vulnerabilities found in multiple operational technology (OT) vendors. CISA is issuing this advisory to provide notice of the reported vulnerabilities and identify baseline mitigations for reducing risks to these and other cybersecurity attacks.

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow remote code execution, loss of sensitive information, denial-of-service, or allow an attacker to modify the controller configuration.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Emerson products are affected:

  • Ovation: Version 3.8.0 Feature Pack 1 and prior

3.2 Vulnerability Overview

3.2.1 MISSING AUTHENTICATION FOR CRITICAL FUNCTION CWE-306

The affected product has several protocols that have no authentication, which could allow an attacker to change controller configuration or cause a denial-of-service condition.

CVE-2022-29966 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2022-29966. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.2 INSUFFICIENT VERIFICATION OF DATA AUTHENTICITY CWE-345

The affected product was found to have no authentication of firmware signing and relies on an insecure checksum for integrity. This could allow an attacker to push malicious firmware images, cause a denial-of-service condition, or achieve remote code execution.

CVE-2022-30267 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2022-30267. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Energy
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Daniel dos Santos and Jos Wetzels from Forescout Technologies reported these vulnerabilities to CISA

4. MITIGATIONS

Emerson recommends the following:

  • Upgrade to the currently available release of Ovation 3.8.0 Feature Pack 3 for remediation of many of the identified vulnerabilities.
  • Users are advised to consider the use of OCR3000 controllers, which offer an extra layer of protection that is not available to older controller models.
  • Deploy and configure Ovation systems and related components as described in the Cybersecurity for Ovation Systems manual (OVREF1000). Ovation Users' Group Website (User Manuals | Reference Manuals) (login required)
  • Users with questions or concerns regarding the impact of these vulnerabilities on Ovation should contact the
    Ovation-CERT by email or phone (1-800-445-9723, option 3).

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • June 6, 2024: Initial Publication

CISA Releases Four Industrial Control Systems Advisories

By: CISA
6 June 2024 at 08:00

CISA released four Industrial Control Systems (ICS) advisories on June 6, 2024. These advisories provide timely information about current security issues, vulnerabilities, and exploits surrounding ICS.

CISA encourages users and administrators to review the newly released ICS advisories for technical details and mitigations.

Mitsubishi Electric CC-Link IE TSN Industrial Managed Switch

By: CISA
6 June 2024 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 5.1
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Mitsubishi Electric
  • Equipment: CC-Link IE TSN Industrial Managed Switch
  • Vulnerability: Allocation of Resources Without Limits or Throttling

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to cause a temporary denial-of service (DoS) condition in the web service on the product.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of CC-Link IE TSN Industrial Managed Switch are affected:

  • NZ2MHG-TSNT8F2: Versions 05 and prior
  • NZ2MHG-TSNT4: Versions 05 and prior

3.2 Vulnerability Overview

3.2.1 Allocation of Resources Without Limits or Throttling CWE-770

Mitsubishi Electric CC-Link IE TSN Industrial Managed Switch has an OpenSSL vulnerability that allows an attacker to cause a temporary denial-of service (DoS) condition on the web service of the product by getting a legitimate administrator user to import specially crafted certificate that makes the product experience notable to very long delays.

CVE-2023-2650 has been assigned to this vulnerability. A CVSS v3.1 base score of 2.7 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:L).

A CVSS v4 score has also been calculated forCVE-2023-2650. A base score of 5.1 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:N/VI:N/VA:L/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Japan

3.4 RESEARCHER

Mitsubishi Electric reported this vulnerability to CISA.

4. MITIGATIONS

Mitsubishi Electric recommends users to update to the fixed versions by following the steps below.

[Fixed versions]

  • CC-Link IE TSN Industrial Managed Switch NZ2MHG-TSNT8F2: Version "06" or later
  • CC-Link IE TSN Industrial Managed Switch NZ2MHG-TSNT4: Version "06" or later

[Update steps]

  1. Contact your local Mitsubishi Electric representative to obtain the fixed firmware version file for CC-Link IE TSN Industrial Managed Switch.
  2. After logging into NZ2MHG-TSNT8F2 or NZ2MHG-TSNT4 through the web interface, update the firmware to the fixed firmware version file mentioned in the above 1. by the function of [System] -> [System Management] -> [Firmware Upgrade] from Function menu. For the detailed procedures, please refer to "CC-Link IE TSN Industrial Managed Switch User's Manual (SH-082449ENG)".

Mitsubishi Electric recommends that customers take the following mitigations to minimize the risk of exploiting this vulnerability:

  • When internet access is required, use a virtual private network (VPN) or other means to prevent unauthorized access.
  • Use the products within a LAN and block access from untrusted networks and hosts.
  • Restrict physical access to the product and your computer and network equipment on the same network.
  • After you log into NZ2MHG-TSNT8F2 or NZ2MHG-TSNT4 through the web interface, change user name and password from default setting at [Account Management] displayed on the function menu. Also, set the proper access permissions for the users.

For additional information see Mitsubishi Electric advisory 2024-002

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • June 6, 2024: Initial Publication

Emerson PACSystem and Fanuc

By: CISA
6 June 2024 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 5.6
  • ATTENTION: Low attack complexity
  • Vendor: Emerson
  • Equipment: PACSystem, Fanuc
  • Vulnerabilities: Cleartext Transmission of Sensitive Information, Insufficient Verification of Data Authenticity Insufficiently Protected Credentials, Download of Code Without Integrity Check

CISA is aware of a public report, known as "OT:ICEFALL", detailing vulnerabilities found in multiple operational technology (OT) vendors. CISA is issuing this advisory to provide notice of the reported vulnerabilities and identify baseline mitigations for reducing risks to these and other cybersecurity attacks.

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow remote code execution, loss of sensitive information, or a denial-of-service condition.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Emerson products are affected:

  • PAC Machine Edition: All versions (CVE-2022-30263, CVE-2022-30265)
  • PACSystem RXi: All versions (CVE-2022-30263, CVE-2022-30268, CVE-2022-30266)
  • PACSystem RX3i: All versions (CVE-2022-30263, CVE-2022-30268, CVE-2022-30265)
  • PACSystem RSTi-EP: All versions (CVE-2022-30263, CVE-2022-30268, CVE-2022-30266, CVE-2022-30265)
  • PACSystem VersaMax: All versions (CVE-2022-30263, CVE-2022-30265)
  • Fanuc VersaMax: All versions (CVE-2022-30263, CVE-2022-30268, CVE-2022-30266)

3.2 Vulnerability Overview

3.2.1 CLEARTEXT TRANSMISSION OF SENSITIVE INFORMATION CWE-319

The affected product utilizes a protocol that allows cleartext transmission of credentials. This could allow an attacker to retrieve these over the network and gain control of the PLC, but cryptographically secure authentication using the SRP-6a protocol is supported and recommended. Enabling authentication on the PLC prevents replay attacks, and requires the attacker to intercept and modify an active connection. Implementation of a non-routing control network also requires compromise of the network topology before SRTP packets can be intercepted.

CVE-2022-30263 has been assigned to this vulnerability. A CVSS v3.1 base score of 5.9 has been calculated; the CVSS vector string is (AV:P/AC:L/PR:N/UI:R/S:U/C:N/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2022-30263. A base score of 4.4 has been calculated; the CVSS vector string is (CVSS4.0/AV:P/AC:L/AT:P/PR:N/UI:A/VC:N/VI:H/VA:H/SC:N/SI:N/SA:N)

3.2.2 INSUFFICIENT VERIFICATION OF DATA AUTHENTICITY CWE-345

The affected products use the Winloader utility to manage firmware updates by serial port or a serial-over-Ethernet link that were found to not use authentication. This could allow an attacker to push malicious firmware images to the controller and cause a denial-of-service condition or allow remote code execution. This vulnerability only effects version of the CPE302, 205, and 310 that were produced before the "-Bxxx" hardware revisions.

CVE-2022-30268 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.9 has been calculated; the CVSS vector string is (AV:P/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:L).

A CVSS v4 score has also been calculated for CVE-2022-30268. A base score of 5.2 has been calculated; the CVSS vector string is (CVSS4.0/AV:P/AC:L/AT:N/PR:L/UI:N/VC:N/VI:H/VA:L/SC:N/SI:N/SA:N)

3.2.3 INSUFFICIENTLY PROTECTED CREDENTIALS CWE-522

The affected product uses a simple hashing scheme by client-side JavaScript. This could allow an attacker to intercept the hashes and strip the hashing scheme to obtain the credentials in plaintext. These credentials are only valid for 5 minutes due to the TLS protocol used, and also requires physical presence to press a button on the device, limiting this attack to being physically present and in a very short window. If this is accomplished, this only allows the attacker to upgrade or downgrade the firmware version. Due to this threat of Man-in-the-Middle attack, documentation recommends limiting physical access to networking equipment, and disabling IP routing on control networks. This vulnerability does not apply to older PLCs without a network-based update process.

CVE-2022-30266 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.0 has been calculated; the CVSS vector string is (AV:P/AC:H/PR:N/UI:R/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2022-30266. A base score of 4.1 has been calculated; the CVSS vector string is (CVSS4.0/AV:P/AC:H/AT:N/PR:N/UI:A/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N)

3.2.4 DOWNLOAD OF CODE WITHOUT INTEGRITY CHECK CWE-494

Control logic downloaded to the PLC, which can be either written in one of the IEC 61131-3 languages or written in C and supplied as an ELF binary block, is not cryptographically authenticated.

CVE-2022-30265 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.4 has been calculated; the CVSS vector string is AV:L/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:N).

A CVSS v4 score has also been calculated for CVE-2022-30265. A base score of 5.6 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:P/PR:H/UI:N/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N)

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Energy
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Daniel dos Santos and Jos Wetzels from Forescout Technologies reported these vulnerabilities to CISA.

4. MITIGATIONS

Emerson recommends the following:

Emerson has updated the Fanuc VersaMax Secure Deployment Guide (GFK-2955D) to include the above recommendations for CVE-2022-30268.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • June 6, 2024: Initial Publication

Johnson Controls Software House iStar Pro Door Controller

By: CISA
6 June 2024 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 9.1
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Johnson Controls Inc.
  • Equipment: Software House iStar Pro Door Controller, ICU
  • Vulnerability: Missing Authentication for Critical Function

2. RISK EVALUATION

Successful exploitation of this vulnerability may allow an attacker to perform a machine-in-the-middle attack to inject commands which change configuration or initiate manual door control commands.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Johnson Controls reports that the following products are affected:

  • Software House iStar Pro Door Controller: All versions
  • ICU: version 6.9.2.25888 and prior

3.2 Vulnerability Overview

3.2.1 Missing Authentication for Critical Function CWE-306

Under certain circumstances, communication between the ICU tool and an iStar Pro door controller is susceptible to machine-in-the-middle attacks which could impact door control and configuration.

CVE-2024-32752 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-32752. A base score of 8.8 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Ireland

3.4 RESEARCHER

Reid Wightman of Dragos reported this vulnerability to Johnson Controls, Inc.

4. MITIGATIONS

The iSTAR Pro controller has reached its end-of-support period and no further firmware updates will be provided. However, the iSTAR Pro has a physical dip switch located on its GCM board, labeled S4, that can be configured to block out communications to the ICU tool. Please consult the iSTAR Pro Installation and Configuration Guide for more details on how to set the dip switch to mitigate this vulnerability.

For more detailed mitigation instructions, please see Johnson Controls Product Security Advisory JCI-PSA-2024-06 v1

Aligning with CISA recommendations, Johnson Controls recommends taking steps to minimize risks to all building automation systems.

CISA provides a section for control systems security recommended practices on the ICS web page on us-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with defense-in-depth strategies.

Further ICS security notices and product security guidance are located at Johnson Controls product security website
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • June 6, 2024: Initial Publication

CISA Releases Four Industrial Control Systems Advisories

By: CISA
4 June 2024 at 08:00

CISA released four Industrial Control Systems (ICS) advisories on June 4, 2024. These advisories provide timely information about current security issues, vulnerabilities, and exploits surrounding ICS.

CISA encourages users and administrators to review the newly released ICS advisories for technical details and mitigations.

Uniview NVR301-04S2-P4

By: CISA
4 June 2024 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 4.8
  • ATTENTION: Exploitable remotely/low attack complexity/public exploits available
  • Vendor: Uniview
  • Equipment: NVR301-04S2-P4
  • Vulnerability: Cross-site Scripting

2. RISK EVALUATION

An attacker could send a user a URL that if clicked on could execute malicious JavaScript in their browser.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following version of Uniview NVR, a network video recorder, is affected:

  • NVR301-04S2-P4: Versions prior to NVR-B3801.20.17.240507

3.2 Vulnerability Overview

3.2.1 Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') CWE-79

The affected product is vulnerable to reflected cross-site scripting attack (XSS). An attacker could send a user a URL that if clicked on could execute malicious JavaScript in their browser. This vulnerability also requires authentication before it can be exploited, so the scope and severity is limited. Also, even if JavaScript is executed, no additional benefits are obtained.

CVE-2024-3850 has been assigned to this vulnerability. A CVSS v3.1 base score of 5.4 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:R/S:C/C:L/I:L/A:N).

A CVSS v4 score has also been calculated for CVE-2024-3850. A base score of 4.8 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:A/VC:L/VI:L/VA:N/SC:L/SI:L/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: China

3.4 RESEARCHER

CISA discovered a public Proof of Concept (PoC) as authored by Bleron Rrustemi and reported it to Uniview.

4. MITIGATIONS

Uniview encourages users to obtain the fixed version, Uniview NVR-B3801.20.17.240507, and update. You may contact your local dealer, Uniview Service Hotline, or regional technical support for assistance.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
    CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

5. UPDATE HISTORY

  • June 4, 2024: Initial Publication

Snowflake Recommends Customers Take Steps to Prevent Unauthorized Access

By: CISA
3 June 2024 at 08:00

On June 2, Snowflake indicated a recent increase in cyber threat activity targeting customer accounts on its cloud data platform. Snowflake issued a recommendation for users to query for unusual activity and conduct further analysis to prevent unauthorized user access.
 
Users and administrators are encouraged to hunt for any malicious activity, report positive findings to CISA, and review the following Snowflake notice for additional information:
•    Detecting and Preventing Unauthorized User Access: Instructions
 

CISA Adds One Known Exploited Vulnerability to Catalog

By: CISA
3 June 2024 at 08:00

CISA has added one new vulnerability to its Known Exploited Vulnerabilities Catalog, based on evidence of active exploitation.

  • CVE-2017-3506 Oracle WebLogic Server OS Command Injection Vulnerability

These types of vulnerabilities are frequent attack vectors for malicious cyber actors and pose significant risks to the federal enterprise.

Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the Known Exploited Vulnerabilities Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information.

Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria.

Fuji Electric Monitouch V-SFT (Update A)

By: CISA
30 May 2024 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.5
  • ATTENTION: Low attack complexity
  • Vendor: Fuji Electric
  • Equipment: Monitouch V-SFT
  • Vulnerabilities: Out-of-Bounds Write, Stack-Based Buffer Overflow, Type Confusion

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to execute arbitrary code.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Fuji Electric's Monitouch V-SFT, a screen configuration software, are affected:

  • Monitouch V-SFT: Versions prior to 6.2.3.0

3.2 Vulnerability Overview

3.2.1 OUT-OF-BOUNDS WRITE CWE-787

The affected product is vulnerable to an out-of-bounds write because of a type confusion, which could result in arbitrary code execution.

CVE-2024-5271 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-5271. A base score of 8.5 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.2 STACK-BASED BUFFER OVERFLOW CWE-121

The affected product is vulnerable to a stack-based buffer overflow, which could allow an attacker to execute arbitrary code.

CVE-2024-34171 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-34171. A base score of 8.5 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.3 ACCESS OF RESOURCE USING INCOMPATIBLE TYPE ('TYPE CONFUSION') CWE-843

The affected product is vulnerable to a type confusion, which could cause a crash or code execution.

CVE-2024-5597 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-5597. A base score of 8.5 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing, Energy
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Japan

3.4 RESEARCHER

kimiy, working with Trend Micro Zero Day Initiative, reported these vulnerabilities to CISA.

4. MITIGATIONS

Fuji Electric recommends users update the product to Monitouch V-SFT v6.2.3.0.

CISA recommends users take defensive measures to minimize the risk of exploitation of this these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. These vulnerabilities are not exploitable remotely.

5. UPDATE HISTORY

  • May 30, 2024: Initial Publication
  • Update A: Added Type confusion vulnerability

Baxter Welch Allyn Configuration Tool

By: CISA
30 May 2024 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.4
  • ATTENTION: Exploitable remotely
  • Vendor: Baxter
  • Equipment: Welch Allyn Configuration Tool
  • Vulnerability: Insufficiently Protected Credentials

2. RISK EVALUATION

Successful exploitation of this vulnerability could lead to the unintended exposure of credentials to unauthorized users.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Baxter (formerly Hillrom and Welch Allyn) products, are affected:

  • Welch Allyn Product Configuration Tool: Versions 1.9.4.1 and prior

3.2 Vulnerability Overview

3.2.1 INSUFFICIENTLY PROTECTED CREDENTIALS CWE-522

Any credentials that were used for authentication or input while using the Welch Allyn Configuration Tool have the potential to be compromised and should be changed immediately.

CVE-2024-5176 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.6 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:C/C:H/I:H/A:L).

A CVSS v4 score has also been calculated for CVE-2024-5176. A base score of 9.4 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:P/VC:H/VI:H/VA:L/SC:H/SI:H/SA:L).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Healthcare and Public Health
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Baxter reported this vulnerability to CISA.

4. MITIGATIONS

Baxter has found no evidence to date of any compromise of personal or health data. Baxter will release a software update for all impacted software to address this vulnerability. A new version of the product that mitigates the vulnerability will be available as follows:

  • Welch Allyn Product Configuration Tool versions 1.9.4.2: Available Q3 2024
  • No user action will be required once the update is released.

Baxter recommends the following workarounds to help reduce risk:

  • Apply proper network and physical security controls.
  • The Welch Allyn Configuration Tool has been removed from public access. Customers are advised to contact Baxter Technical Support or their Baxter Project Manager to create configuration files, as needed. Baxter Technical Support can be reached at (800)535-6663, option 2.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • May 30, 2024: Initial Publication

CISA Adds Two Known Exploited Vulnerabilities to Catalog

By: CISA
30 May 2024 at 08:00

CISA has added one new vulnerability to its Known Exploited Vulnerabilities Catalog, based on evidence of active exploitation.

  • CVE-2024-24919 Check Point Quantum Security Gateways Information Disclosure Vulnerability
  • CVE-2024-1086 Linux Kernel Use-After-Free Vulnerability

These types of vulnerabilities are frequent attack vectors for malicious cyber actors and pose significant risks to the federal enterprise.

Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the Known Exploited Vulnerabilities Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information.

Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria.

Inosoft VisiWin

By: CISA
30 May 2024 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.5
  • ATTENTION: Low attack complexity/public exploits are available
  • Vendor: Inosoft
  • Equipment: VisiWin
  • Vulnerability: Incorrect Default Permissions

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to gain SYSTEM privileges.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Inosoft products are affected:

  • VisiWin 7: All versions prior to version 2024-1

3.2 Vulnerability Overview

3.2.1 INCORRECT DEFAULT PERMISSIONS CWE-276

VisiWin creates a directory with insufficient permissions, allowing a low-level user the ability to add and modify certain files that hold SYSTEM privileges, which could lead to privilege escalation.

CVE-2023-31468 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H)

A CVSS v4 score has also been calculated for CVE-2023-31468. A base score of 8.5 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

CISA discovered a PoC (Proof of concept) as authored by Carlo Di Dato and reported it to Inosoft.

4. MITIGATIONS

Inosoft recommends users to update to VisiWin version 2024-1.

For more information, please visit VisiWin's support page.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
    CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • May 30, 2024: Initial Publication

Baxter Welch Allyn Connex Spot Monitor

By: CISA
30 May 2024 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.1
  • ATTENTION: Exploitable remotely
  • Vendor: Baxter
  • Equipment: Welch Allyn Connex Spot Monitor (CSM)
  • Vulnerability: Use of Default Cryptographic Key

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to modify device configuration and firmware data. Tampering with this data could lead to device compromise, resulting in impact and/or delay in patient care.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Baxter (formerly manufactured by Hillrom) medical devices are affected:

  • Welch Allyn Connex Spot Monitor (CSM): Versions 1.52 and prior

3.2 Vulnerability Overview

3.2.1 USE OF DEFAULT CRYPTOGRAPHIC KEY CWE-1394

The impacted product uses a default cryptographic key for potentially critical functionality. An attacker could modify device configurations and firmware data, resulting in impact and/or delay in patient care.

CVE-2024-1275 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.4 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:N).

A CVSS v4 score has also been calculated for CVE-2024-1275. A base score of 9.1 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:H/AT:N/PR:N/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Healthcare and Public Health
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Maarten Boone and Edwin Van Andel (CTO of Zerocopter) reported this vulnerability to Baxter.

4. MITIGATIONS

Baxter has released a software update for all impacted devices and software to address this vulnerability. A new version of the product that mitigates the vulnerability is available as follows:

  • Welch Allyn Connex Spot Monitor: Version 1.52.01 (available October 16, 2023)

Baxter recommends users upgrade to the latest versions of their products. Information on how to update products to their new versions can be found on the Baxter disclosure page or the Hillrom disclosure page.

Baxter recommends the following workarounds to help reduce risk:

  • Apply proper network and physical security controls.
  • Ensure a unique encryption key is configured and applied to the product (as described in the Connex Spot Monitor Service Manual).

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • May 30, 2024: Initial Publication

LenelS2 NetBox

By: CISA
30 May 2024 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.3
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: LenelS2
  • Equipment: NetBox
  • Vulnerabilities: Use of Hard-coded Password, OS Command Injection, Argument Injection

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to bypass authentication and execute malicious commands with elevated permissions

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following products of LenelS2, a Carrier Brand, are affected:

  • NetBox: All versions prior to 5.6.2

3.2 Vulnerability Overview

3.2.1 USE OF HARD-CODED PASSWORD CWE-259

LenelS2 NetBox access control and event monitoring system was discovered to contain hard-coded credentials in versions prior to and including 5.6.1, which allows an attacker to bypass authentication requirements.

CVE-2024-2420 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-2420. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.2 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND ('OS COMMAND INJECTION') CWE-78

LenelS2 NetBox access control and event monitoring system was discovered to contain an unauthenticated remote code execution in versions prior to and including 5.6.1, which allows an attacker to execute malicious commands with elevated permissions.

CVE-2024-2421 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:H/UI:N/S:C/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-2421. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:L/SI:H/SA:L).

3.2.3 IMPROPER NEUTRALIZATION OF ARGUMENT DELIMITERS IN A COMMAND ('ARGUMENT INJECTION') CWE-88

LenelS2 NetBox access control and event monitoring system was discovered to contain an authenticated remote code execution in versions prior to and including 5.6.1, which allows an attacker to execute malicious commands.

CVE-2024-2422 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-2422. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Noam Moshe of Claroty Team82 reported these vulnerabilities to CISA.

4. MITIGATIONS

These vulnerabilities have been mitigated in NetBox release 5.6.2. It is strongly recommended that users upgrade to NetBox release 5.6.2 by contacting their authorized installer.
Users should follow recommended deployment guidelines found in the NetBox hardening guide found in the NetBox built-in help menu.

For more information, see Carrier's security bulletin for LenelS2.

CISA recommends users take defensive measures to minimize the risk of exploitation of this these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • May 30, 2024: Initial Publication

Westermo EDW-100

By: CISA
30 May 2024 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 9.8
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Westermo
  • Equipment: EDW-100
  • Vulnerabilities: Use of Hard-coded Password, Insufficiently Protected Credentials

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to access the device using hardcoded credentials and download cleartext username and passwords.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Westermo EDW-100, a Serial to Ethernet converter, are affected:

  • EDW-100: All versions

3.2 Vulnerability Overview

3.2.1 Use of Hard-coded Password CWE-259

Westermo EDW-100 has a hidden administrator account with a hardcoded password. In the firmware package, in "image.bin", the username root and the password for this account are both hard-coded and exposed as strings that can trivially be extracted. Currently there is no way to change this password.

CVE-2024-36080 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-36080. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.2 Insufficiently Protected Credentials CWE-522

Westermo EDW-100 allows an unauthenticated GET request that can download the configuration-file that contains the configuration, username, and passwords in clear-text.

CVE-2024-36081 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-36081. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Energy, Water and Wastewater Systems, Transportation Systems
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Sweden

3.4 RESEARCHER

Nicolai Grødum and Sofia Lindqvist of PwC Norway reported these vulnerabilities to CISA.

4. MITIGATIONS

To mitigate the risks associated with these vulnerabilities, Westermo recommends:

Network segregation, perimeter protection, network to network protection, and physical security measures. EDW-100 functions as an industrial serial to ethernet converter. This means that EDW-100 does not in itself have any of the protective measures you require in a modern security posture, EDW-100 should not be placed at the edge of the network but instead deployed using the techniques mentioned in the IEC 62443 standard.

This means the use of network segregation and perimeter protection which can be accomplished by for example deploying a firewall and the use of VLANs.

If data needs to flow into, or out of, the security zone containing EDW-100 it is important to have network to network protection enabled which for example can be applied with a Virtual Private Network (VPN).

It is also crucial to have physical security measures put in place as the unit can be vulnerable to physical attacks and tampering. A recommendation to mitigate this risk is to place the unit in a separate enclosure with locks and alarms if it opened outside of normal maintenance.

While the unit's design characteristics may necessitate extra precautions, implementing the suggested countermeasures ensures a secure deployment that effectively addresses associated risks.

Westermo recommends replacing EDW-100 with Lynx DSS L105-S1. For further reference see 5-Port Managed Industrial Device Server Switch | L105-S1 ᐈ Westermo.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • May 30, 2024: Initial Publication

CISA Releases Seven Industrial Control Systems Advisories

By: CISA
30 May 2024 at 08:00

CISA released seven Industrial Control Systems (ICS) advisories on May 30, 2024. These advisories provide timely information about current security issues, vulnerabilities, and exploits surrounding ICS.

CISA encourages users and administrators to review the newly released ICS advisories for technical details and mitigations.

CISA Adds One Known Exploited Vulnerability to Catalog

By: CISA
29 May 2024 at 08:00

CISA has added one new vulnerability to its Known Exploited Vulnerabilities Catalog, based on evidence of active exploitation.

  • CVE-2024-4978 Justice AV Solutions (JAVS) Viewer Installer Embedded Malicious Code Vulnerability

These types of vulnerabilities are frequent attack vectors for malicious cyber actors and pose significant risks to the federal enterprise.

Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the Known Exploited Vulnerabilities Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information.

Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria.

CISA Adds One Known Exploited Vulnerability to Catalog

By: CISA
28 May 2024 at 08:00

CISA has added one new vulnerability to its Known Exploited Vulnerabilities Catalog, based on evidence of active exploitation.

These types of vulnerabilities are frequent attack vectors for malicious cyber actors and pose significant risks to the federal enterprise.

Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the Known Exploited Vulnerabilities Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information.

Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria.

Campbell Scientific CSI Web Server

By: CISA
28 May 2024 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 6.9
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Campbell Scientific
  • Equipment: CSI Web Server
  • Vulnerabilities: Path Traversal, Weak Encoding for Password

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to download files and decode stored passwords.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Campbell Scientific CSI Web Server and RTMC (Real-Time Monitoring and Control) Pro, which contains the CSI Web Server are affected:

  • Campbell Scientific CSI Web Server: Versions 1.6 and prior
  • RTMC Pro: Version 5.0 and prior

3.2 Vulnerability Overview

3.2.1 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY ('PATH TRAVERSAL') CWE-22

The Campbell Scientific CSI Web Server supports a command that will return the most recent file that matches a given expression. A specially crafted expression can lead to a path traversal vulnerability. This command combined with a specially crafted expression allows anonymous, unauthenticated access (allowed by default) by an attacker to files and directories outside of the webserver root directory they should be restricted to.

CVE-2024-5433 has been assigned to this vulnerability. A CVSS v3.1 base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2024-5433. A base score of 6.9 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:L/VI:L/VA:N/SC:N/SI:N/SA:N).

3.2.2 WEAK ENCODING FOR PASSWORD CWE-261

The Campbell Scientific CSI Web Server stores web authentication credentials in a file with a specific file name. Passwords within that file are stored in a weakly encoded format. There is no known way to remotely access the file unless it has been manually renamed. However, if an attacker were to gain access to the file, passwords could be decoded and reused to gain access.

CVE-2024-5434 has been assigned to this vulnerability. A CVSS v3.1 base score of 5.7 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2024-5434. A base score of 6.9 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:L/VI:L/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Energy, Food and Agriculture, Water and Wastewater, and Transportation Systems
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Patrick K. Sheehan, Grant Hume, and Donald Macary reported these vulnerabilities to CISA.

4. MITIGATIONS

Campbell Scientific recommends users to update to the version.
For user of CSI Web Server update to the most recent CSI Web Server 1.x patch

For users of RTMC Pro 5 update to the most recent RTMC Pro 5.x patch

For users of RTMC Pro 4 update to the most recent RTMC Pro 4.x patch.

Contact Campbell Scientific for more details.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • May 28, 2024: Initial Publication

CISA Releases One Industrial Control Systems Advisory

By: CISA
28 May 2024 at 08:00

CISA released one Industrial Control Systems (ICS) advisory on May 28, 2024. These advisories provide timely information about current security issues, vulnerabilities, and exploits surrounding ICS.

CISA encourages users and administrators to review newly released ICS advisories for technical details and mitigations.

Cisco Releases May 2024 Cisco ASA, FMC, and FTD Software Security Publication

By: CISA
24 May 2024 at 08:00

Cisco released a bundled publication for security advisories that address vulnerabilities in Cisco Adaptive Security Appliance (ASA), Firepower Management Center (FMC), and Firepower Threat Defense (FTD) software. A cyber threat actor could exploit one of these vulnerabilities to take control of an affected system.

Users and administrators are encouraged to review the following publication and apply necessary updates:

CISA Releases One Industrial Control Systems Advisory

By: CISA
23 May 2024 at 08:00

CISA released one Industrial Control Systems (ICS) advisory on May 23, 2024. These advisories provide timely information about current security issues, vulnerabilities, and exploits surrounding ICS.

CISA encourages users and administrators to review newly released ICS advisories for technical details and mitigations.

CISA Adds One Known Exploited Vulnerability to Catalog

By: CISA
23 May 2024 at 08:00

CISA has added one new vulnerability to its Known Exploited Vulnerabilities Catalog, based on evidence of active exploitation.

These types of vulnerabilities are frequent attack vectors for malicious cyber actors and pose significant risks to the federal enterprise.

Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the Known Exploited Vulnerabilities Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information.

Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria.

AutomationDirect Productivity PLCs

By: CISA
23 May 2024 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.3
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: AutomationDirect
  • Equipment: Productivity PLCs
  • Vulnerabilities: Buffer Access with Incorrect Length Value, Out-of-bounds Write, Stack-based Buffer Overflow, Improper Access Control, Active Debug Code, Insufficient Verification of Data Authenticity

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could lead to remote code execution and denial of service.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

AutomationDirect reports the following versions of Productivity PLCs are affected:

  • Productivity 3000 P3-550E CPU: FW 1.2.10.9
  • Productivity 3000 P3-550E CPU: SW 4.1.1.10
  • Productivity 3000 P3-550 CPU: FW 1.2.10.9
  • Productivity 3000 P3-550 CPU: SW 4.1.1.10
  • Productivity 3000 P3-530 CPU: FW 1.2.10.9
  • Productivity 3000 P3-530 CPU: SW 4.1.1.10
  • Productivity 2000 P2-550 CPU: FW 1.2.10.10
  • Productivity 2000 P2-550 CPU: SW 4.1.1.10
  • Productivity 1000 P1-550 CPU: FW 1.2.10.10
  • Productivity 1000 P1-550 CPU: SW 4.1.1.10
  • Productivity 1000 P1-540 CPU: FW 1.2.10.10
  • Productivity 1000 P1-540 CPU: SW 4.1.1.10

3.2 Vulnerability Overview

3.2.1 Buffer Access with Incorrect Length Value CWE-805

A heap-based buffer overflow vulnerability exists in the Programming Software Connection FiBurn functionality of AutomationDirect P3-550E 1.2.10.9. A specially crafted network packet can lead to a buffer overflow. An attacker can send an unauthenticated packet to trigger this vulnerability.

CVE-2024-24851 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2024-24851. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).

3.2.2 Out-of-bounds Write CWE-787

A length exceeded buffer overflow vulnerability exists in the Programming Software Connection CurrDir functionality of AutomationDirect P3-550E 1.2.10.9. A specially crafted network packet can lead to a denial of service. An attacker can send an unauthenticated packet to trigger this vulnerability.

CVE-2024-24946 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:H).

A CVSS v4 score has also been calculated for CVE-2024-24946. A base score of 8.8 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:L/VA:H/SC:N/SI:N/SA:N).

3.2.3 Out-of-bounds Write CWE-787

An allocation failed buffer overflow vulnerability exists in the Programming Software Connection CurrDir functionality of AutomationDirect P3-550E 1.2.10.9. A specially crafted network packet can lead to a denial of service. An attacker can send an unauthenticated packet to trigger this vulnerability.

CVE-2024-24947 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:H).

A CVSS v4 score has also been calculated for CVE-2024-24947. A base score of 8.8 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:L/VA:H/SC:N/SI:N/SA:N).

3.2.4 Out-of-bounds Write CWE-787

A null-byte write vulnerability exists in the Programming Software Connection FileSystem API functionality of AutomationDirect P3-550E 1.2.10.9. Specially crafted network packets can lead to heap-based memory corruption. An attacker can send malicious packets to trigger these vulnerabilities.

CVE-2024-24954 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:H).

A CVSS v4 score has also been calculated for CVE-2024-24954. A base score of 8.8 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:L/VA:H/SC:N/SI:N/SA:N).

3.2.5 Out-of-bounds Write CWE-787

A null-byte write vulnerability exists in the Programming Software Connection FileSystem API functionality of AutomationDirect P3-550E 1.2.10.9. Specially crafted network packets can lead to heap-based memory corruption. An attacker can send malicious packets to trigger these vulnerabilities.

CVE-2024-24955 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:H).

A CVSS v4 score has also been calculated for CVE-2024-24955. A base score of 8.8 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:L/VA:H/SC:N/SI:N/SA:N).

3.2.6 Out-of-bounds Write CWE-787

A null-byte write vulnerability exists in the Programming Software Connection FileSystem API functionality of AutomationDirect P3-550E 1.2.10.9. Specially crafted network packets can lead to heap-based memory corruption. An attacker can send malicious packets to trigger these vulnerabilities.

CVE-2024-24956 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:H).

A CVSS v4 score has also been calculated for CVE-2024-24956. A base score of 8.8 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:L/VA:H/SC:N/SI:N/SA:N).

3.2.7 Out-of-bounds Write CWE-787

A null-byte write vulnerability exists in the Programming Software Connection FileSystem API functionality of AutomationDirect P3-550E 1.2.10.9. Specially crafted network packets can lead to heap-based memory corruption. An attacker can send malicious packets to trigger these vulnerabilities.

CVE-2024-24957 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:H).

A CVSS v4 score has also been calculated for CVE-2024-24957. A base score of 8.8 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:L/VA:H/SC:N/SI:N/SA:N).

3.2.8 Out-of-bounds Write CWE-787

A null-byte write vulnerability exists in the Programming Software Connection FileSystem API functionality of AutomationDirect P3-550E 1.2.10.9. Specially crafted network packets can lead to heap-based memory corruption. An attacker can send malicious packets to trigger these vulnerabilities.

CVE-2024-24958 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:H).

A CVSS v4 score has also been calculated for CVE-2024-24958. A base score of 8.8 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:L/VA:H/SC:N/SI:N/SA:N).

3.2.9 Out-of-bounds Write CWE-787

A null-byte write vulnerability exists in the Programming Software Connection FileSystem API functionality of AutomationDirect P3-550E 1.2.10.9. Specially crafted network packets can lead to heap-based memory corruption. An attacker can send malicious packets to trigger these vulnerabilities.

CVE-2024-24959 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:H).

A CVSS v4 score has also been calculated for CVE-2024-24959. A base score of 8.8 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:L/VA:H/SC:N/SI:N/SA:N).

3.2.10 Stack-based Buffer Overflow CWE-121

A stack-based buffer overflow vulnerability exists in the Programming Software Connection FileSelect functionality of AutomationDirect P3-550E 1.2.10.9. A specially crafted network packet can lead to stack-based buffer overflow. An attacker can send an unauthenticated packet to trigger this vulnerability.

CVE-2024-24962 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-24962. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.11 Stack-based Buffer Overflow CWE-121

A stack-based buffer overflow vulnerability exists in the Programming Software Connection FileSelect functionality of AutomationDirect P3-550E 1.2.10.9. A specially crafted network packet can lead to stack-based buffer overflow. An attacker can send an unauthenticated packet to trigger this vulnerability.

CVE-2024-24963 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-24963. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.12 Improper Access Control CWE-284

A write-what-where vulnerability exists in the Programming Software Connection Remote Memory Diagnostics functionality of AutomationDirect P3-550E 1.2.10.9. A specially crafted network packet can lead to an arbitrary write. An attacker can send an unauthenticated packet to trigger this vulnerability.

CVE-2024-22187 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-22187. A base score of 8.8 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.13 Improper Access Control CWE-284

A read-what-where vulnerability exists in the Programming Software Connection IMM 01A1 Memory Read functionality of AutomationDirect P3-550E 1.2.10.9. A specially crafted network packet can lead to a disclosure of sensitive information. An attacker can send an unauthenticated packet to trigger this vulnerability.

CVE-2024-23315 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2024-23315. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.2.14 Active Debug Code CWE-489

Leftover debug code exists in the Telnet Diagnostic Interface functionality of AutomationDirect P3-550E 1.2.10.9. A specially crafted series of network requests can lead to unauthorized access. An attacker can send a sequence of requests to trigger this vulnerability.

CVE-2024-21785 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-21785. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.15 Insufficient Verification of Data Authenticity CWE-345

A code injection vulnerability exists in the scan_lib.bin functionality of AutomationDirect P3-550E 1.2.10.9. A specially crafted scan_lib.bin can lead to arbitrary code execution. An attacker can provide a malicious file to trigger this vulnerability.

CVE-2024-23601 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-23601. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities, Critical Manufacturing, Information Technology
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Matt Wiseman of CISCO TALOS reported these vulnerabilities to AutomationDirect.

4. MITIGATIONS

AutomationDirect recommends that users:

  • Update the Productivity Suite programming software to version 4.2.0.x or higher.
  • Update Productivity PLC's firmware to the latest version.

Although Automation Networks and Systems come equipped with built-in password protection mechanisms, this represents a fraction of the security measures needed to safeguard these systems. It is imperative that Automation Control System Networks integrate data protection and security measures that match, if not exceed, the robustness of conventional business computer systems. AutomationDirect advises users of PLCs, HMI products, and SCADA systems to conduct a thorough network security analysis to ascertain the appropriate level of security necessary for their specific application.

AutomationDirect has identified the following mitigation for instances where systems cannot be upgraded to latest version:

  • Physically disconnect the PLC from any external networks, including the internet, local area networks (LANs), and other interconnected systems.
  • Configure network segmentation to isolate PLC from other devices and systems withing the organization.
  • Implement firewall rules or network access control (NAC) policies to block incoming and outgoing traffic to the PLC.

Please refer to the following link for supporting information related to security considerations. https://support.automationdirect.com/docs/securityconsiderations.pdf

If you have any questions regarding this issue, please contact AutomationDirect Technical Support at 770-844-4200 or 800-633-0405 for further assistance.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • May 23, 2024: Initial Publication